tr

BOILER WATER INHIBITOR KISIR


CONTROL TRIO-hardness, low and high pressure boilers waters and phosphate of calcium and magnesium hardness control to crash in order to provide a powdered product is used.
TRIO-CONTROL dosing with the boiler water hardness calcium and magnesium salts, non-sticky and soft mud are removed it will be converted to bluff with the aid wins out. TRIO-hardness CONTROL, sodium phosphate derivative and can be used easily with TRIO-Alkalinity CONTROL. 40-50 ° C temperature scale, pure water right 20 (condensate, distilled water, etc.) to be solved by joining a scale CONTROL TRIO-hardness is achieved and the prepared solution to the system is made ready for dosing. TRIO-hardness CONTROL dosage, beside water quality will vary depending on the pressure and win. Any application made in the boiler water is not the first dosage of phosphate for 1 ton of water 30-80 gr. is between. Continuous dosing of the water for 1 ton fattening 10-25 gr. is. Product, dosing pumps, with the help of Stim drama, drama or Economizer water input can be dosing. Continuous dosing with the principle should be applied.

TYPICAL PHYSICAL PROPERTIES:

Appearance : white granular powder
Resolution : soluble in water at a rate of 10-15%
Specific Gravity : 1.06 gr/cm3
pH (1% solution) : 8.5-9.0
Alma Flame Temperature : None
Explosion Limit : None


CHEMICAL PACKAGING AND STORAGE OF MATTER:
Packaging shape, 15-20 Kg. pails and storage time in 2 years.


WORKING CONDITIONS SHOULD CONSIDER of the ISSUES:
R-21 Harmful in contact with skin.
R-22 Harmful if swallowed.
S-26 In case of contact with eyes, rinse immediately with plenty of water and seek medical advice.
S-28 in contact with skin, wash immediately with plenty of water.
S-36/37 suitable protective clothing while you work, use protective gloves.
S-39 employees when the appropriate protective eye / face use.
S-62 Do not induce vomiting if swallowed victim. Immediately refer to the first aid service, show the label.

Announcements





Pool